Pumps and Motors Catalogue 2026 - Flipbook - Page 238
WELL AND BOREHOLE PUMPS
CABLE RECOMMENDATION SIZE FOR PUMPS – CABLE SIZE 4 CORE IN MM
MAXIMUM LENGTH OF CABLE IN METRES
MOTOR (Kw)
SINGLE PHASE MOTORS
0.37
0.55
0.75
1.1
1.5
2.2
3 PHASE MOTORS
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
VOLT
1.5mm
2.5mm
4mm
6mm
10mm
16mm
230
230
230
230
230
230
80
55
40
30
25
–
130
90
65
50
35
30
230
140
105
75
60
50
350
200
160
115
90
70
580
350
300
190
145
120
1000
700
500
400
230
185
415
415
415
415
415
415
415
415
415
415
400
315
240
180
135
100
65
50
40
30
500
430
350
285
225
165
110
85
70
55
600
600
500
350
360
255
180
135
110
90
850
700
650
450
470
390
255
195
165
130
1000
900
750
600
600
450
420
330
270
220
1300
1200
1000
900
900
700
560
500
390
495
CABLE RESISTANCE EXAMPLES Max volt drop allowed is 2.5% = 6v @ 230v
1.1 Kw motor single phase on 150m of cable,
ie: on 1.1 Kw the maximum you can run is 190m, if you use 10mm.
1.1 Kw motor three phase on 150m of cable,
ie: 1.1 Kw can go up to 180m on 1.5mm cable. Therefore on 10mm it can run up to 600m.
A
CABLES HO7RNF & JOINTS
ITEM - 4 CORE CABLE
CABLE
1.5 x 4C CABLE
2.5 x 4C CABLE
4.0 x 4C CABLE
6.0 x 4C CABLE
CODE
ITEM - 3 CORE CABLE
CODE
023-510
023-512
023-514
023-516
1.5 x 3C CABLE
2.5 x 3C CABLE
4.0 x 3C CABLE
6.0 x 3C CABLE
023-610
023-612
023-614
023-616
10.0 x 4C CABLE
023-518
10.0 x 3C CABLE
023-620
ITEM
JOINT KIT EPOXY 2 PART 0.5-4mm
JOINT KIT EPOXY 6-10mm
CODE
023-520
023-522
ITEM
THERMAL JOINT KIT
UP TO 2.5mm 4 CORE STD
CODE
023-525
Cut cable cannot be returned for credit unless sent incorrectly.
2 PART EPOXY CABLE JOINING KIT
THERMAL CABLE JOINING KIT
237